7 Detailed Functions
Precautions for Correct Use
Precautions for Correct Use
The Output Frequency Setting/Monitor (F001) shows the frequency reference configured in the
internal memory (RAM).
F001 displays the frequency reference value selected at that time.
If you change the frequency reference value displayed in F001 and save it (by pressing the Enter
key), the data will be stored with the frequency reference selected at that time.
• For the multi-step speed reference 0, the data will be stored with the 1st Multi-step Speed
Reference 0 (A020)/2nd Multi-step Speed Reference 0 (A220)/3rd Multi-step Speed
Reference 0 (A320) according to the 1st/2nd/3rd Control Method selection.
• For the multi-step speed reference 1 to 15, the data will be stored with the corresponding
Multi-step Speed Reference 1 to 15 (A021 to A035).
* The frequency reference selection of Digital Operator (Volume adjuster), Control terminal
block (Analog input), Modbus communication, Options, DriveProgramming, and Operation
function output cannot be changed in F001.
RUN Command Selection
Select the RUN/STOP command selection method.
Parameter No.
A002
Related functions
Below are the details of the parameter data.
Data
Inputs the RUN command via the ON/OFF of the FW/RV signal allocated to the control circuit terminal
block.
01
It will be regarded as the STOP command if both the forward and reverse commands are input
simultaneously.
Inputs the RUN command via the RUN key and the STOP/RESET key on the Digital Operator or LCD
02
Digital Operator.
03
Inputs the RUN command via Modbus communication.
04
Inputs the RUN command via the option board mounted on the option port 1.
05
Inputs the RUN command via the option board mounted on the option port 2.
7 - 18
Function name
RUN Command Selection
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
01: Control circuit terminal block
02: Digital Operator
03: Modbus communication
04: Option 1
05: Option 2
F004, C001 to C008, C019
Frequency reference source
Default data
Unit
02