Omron RX Series User Manual page 78

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

2 Design
Arrangement of Main Circuit Terminals
The arrangement of the inverter main circuit terminals is shown below.
Ro
To
Charge indicator
+1–P/+2
short-circuit bar
[EMC filter function switching method]
Filter disable pin (J62)
EMC filter disabled (factory setting)
EMC filter enabled
R/L1
S/L2
T/L3
G
Ground terminal with
short-circuit bar (shaded area)
for EMC filter function switching
[EMC filter function switching method]
EMC filter enabled
2 - 22
Terminal arrangement
R/L1
S/L2
T/L3
U/T1
+1
RB
P/+2
N/–
When not using the DC reactor,
keep the +1–P/+2 short-circuit
bar attached.
In order to enable the EMC filter
Dummy plug
(green)
function, set up the plug inserted into
the filter enable pin (J61) and filter
disable pin (J62) as shown in the
table below. Confirm that electrical
power
is
performing this setup. Not doing so
Filter enable
may result in electric shock. Also,
pin (J61)
use with the plug inserted.
Short plug
Filter enable pin (J61)
Dummy plug (green)
Short plug
Charge indicator
+1
P/+2
N/–
+1–P/+2
short-circuit bar
When not using the DC reactor,
keep the +1–P/+2 short-circuit
bar attached.
EMC filter disabled (factory setting)
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
3G3RX-A2004-V1 to A2037-V1
3G3RX-A4004-V1 to A4037-V1
V/T2
W/T3
Ro, To: M4
G
G
Ground terminal: M4
Others: M4
disconnected
before
Filter disable pin (J62)
Short plug
Dummy plug (green)
3G3RX-A2055-V1, A2075-V1
Ro
To
3G3RX-A4055-V1, A4075-V1
RB
Ro, To: M4
U/T1
V/T2
W/T3
Ground terminal: M5
Others: M5
G
3G3RX-A2110-V1
3G3RX-A4110-V1
Ro, To: M4
Ground terminal: M5
Others: M6
Applicable model