Switching Operations between a Communications Option Board and
Control Circuit Terminals
You can switch reference input between the Communications Option Board and the control circuit terminals.
Set one of the parameters H1-01 to H1-06 (multi-function contact input terminal S3 to S8 function selection)
to 2 (Option/Inverter selection) to enable switching reference input using the terminal ON/OFF status when
the Inverter is stopped.
Setting Precautions
To switch command inputs between the Communications Option Board and the control circuit terminals, set
the following parameters.
Set b1-01 (Reference Selection) to 1 (Control circuit terminal [analog input])
Set b1-02 (Operation Method Selection to 1 (Control circuit terminal (sequence inputs])
Set one of the parameters H1-01 to H1-06 (multi-function contact input terminal S3 to S8 function selec-
tion) to 2 (Option/Inverter selection).
Terminal Status
Inverter
OFF
(Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
Communications Option Board
ON
(Frequency reference and Run Command are enabled from Communications Option Board.)
Frequency Reference and Run Command Selection
Input Terminal Functions
89