5 Basic Settings

5-10-9 Forward Run Signal (FWR)

• This signal is output while the inverter performs the forward operation.
• While the inverter performs the reverse operation or when stopped, this signal is not output.
• Allocate one of the Multi-function Output P1 to P5 Selection (C021 to C025) or the Multi-function
Relay Output (MA, MB) Function Selection (C026) to 51 (FWR) to enable this function.
Parameter
No.
Multi-function Output P1 to
C021 to C025
P5 Selection
Multi-function Relay Output
C026
(MA, MB) Function Selection

5-10-10 Reverse Run Signal (RVR)

• This signal is output while the inverter performs the reverse operation.
• While the inverter performs the forward operation or when stopped, this signal is not output.
• Allocate one of the Multi-function Output P1 to P5 Selection (C021 to C025) or the Multi-function
Relay Output (MA, MB) Function Selection (C026) to 52 (RVR) to enable this function.
Parameter
No.
Multi-function Output P1 to
C021 to C025
P5 Selection
Multi-function Relay Output
C026
(MA, MB) Function Selection
Output frequency [kHz]
Forward run (FWR) signal
Reverse run (RVR) signal
5 - 64
Function name
51: FWR (Forward run signal)
Function name
52: RVR (Reverse run signal)
Forward
Reverse
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
Default data
05
Data
Default data
05
Unit
Unit