DC Voltage Monitor [d102]
Use this function to display the inverter DC voltage called "P-N voltage" (the DC voltage between the
P/+2 and N/– terminals of the inverter.)
During operation, the monitor value changes according to the actual DC voltage of the inverter.
Parameter No.
d102
Regenerative Braking Load Rate Monitor [d103]
Use this function to display the regenerative braking load rate. If this monitor value exceeds the value
set in the Usage Rate of Regenerative Braking (b090), the inverter will cause a trip with the alarm code
E06 (Braking resistor overload protection).
Parameter No.
d103
Electronic Thermal Load Rate Monitor [d104]
Use this function to display the electronic thermal load rate. If this monitor value exceeds 100%, the
inverter will cause a trip with the alarm code E05 (Overload protection).
Parameter No.
d104
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
DC Voltage Monitor
Function name
Regenerative Braking
Load Rate Monitor
Function name
Electronic Thermal Load
Rate Monitor
Data
0.0 to 999.0 (Displayed in increments of
0.1 V)
Data
0.0 to 100.0 (Displayed in increments of
0.1%)
Data
0.0 to 100.0 (Displayed in increments of
0.1%)
7 Detailed Functions
Default data
Unit
V
Default data
Unit
%
Default data
Unit
%
7 - 13