7 Detailed Functions
AM/AMI Gain Setting
• Use these parameters to set the output gain of the inverter according to the meter connected to the
terminal AM/AMI.
Parameter No.
C106
C107
C109
C110
(Example) If AMI provides an output of 4 to 20 mA: C110 = 4
The relationship between the AM Gain Setting (C106) and the AM Bias Setting (C109) when there
values are changed is as follows.
• C109 = 0 (Offset 0%)
AM output
(AMI output)
C109=0%
(C110=0%)
Note The relationship between the AMI Gain Setting (C106) and the AMI Bias Setting (C110) is similar to this.
7 - 144
Function name
50. to 200.
AM Gain Setting
Set AM monitor gain.
50. to 200.
AMI Gain Setting
Set AMI monitor gain.
0. to 100.
AM Bias Setting
Set AM monitor offset.
0. to 100.
AMI Bias Setting
Set AMI monitor offset.
C106=200%
(C107=200%)
C106=100%
(C107=100%)
C106=50%
(C107=50%)
Select
monitor
Full-scale
Full-scale
value
1/2
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
÷
20 = 20 [%] (Default data)
• C109 = 50 (Offset 50%)
AM output
(AMI output)
C106=200%
(C107=200%)
C109=50%
(C110=50%)
Full-scale
1/2
Default data
Unit
100.
%
0.
20.
C106=100%
(C107=100%)
C106=50%
(C107=50%)
Select
monitor
Full-scale
value