• When the Alarm Code Selection (C062) is set to 01 (3 bits) or 02 (4 bits), the multi-function output
terminals P1 to P3 or P1 to P4 are used forcedly for alarm code output. The following table shows the
alarm codes that will be output.
Multi-function output
terminals
P4
P3
P2
AC3 AC2 AC1 AC0
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
1
0
1
1
1
0
1
1
0
1
1
0
1
1
1
1
1
1
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
With 4-bit code selected
P1
Factor
code
0
Normal
Normal
E01 to
1
Overcurrent protection
E03, E04
Overload protection
0
E05, E38
Overload protection in a low
speed range
Overvoltage/Incoming
1
E07, E15
overvoltage protection
0
E09
Undervoltage protection
1
E16
Power interruption protection
0
E30
IGBT error
Braking resistor overload
1
E06
protection
E08,
EEPROM error, CPU error,
0
E11,
GA communication error,
E23, E25
Main circuit error
1
E10
CT error
E12,
External trip, USP error,
0
E13,
Thermistor error, Brake error
E35, E36
0
E14
Ground protection
Temperature error due to
1
E20
cooling fin speed drop
1
E21
Temperature error
0
E24
Input phase loss protection
E50 to
Network error, Option 1/2
1
E79
error 0 to 9
Factor
Trip data
code
Normal
E01 to
E03, E04
E05
E07, E15
E09
E16
E30
7 Detailed Functions
With 3-bit code selected
Trip data
Normal
Overcurrent protection
Overload protection
Overvoltage/Incoming
overvoltage protection
Undervoltage protection
Power interruption protection
IGBT error
Other errors
7 - 131