Open Channel Monitoring (OCM)
[6 relay model]
An OCM installation is defined one of three ways, based on the Primary Measuring
Device (PMD):
1.
Dimensional (P600 = 2,3,6,7)
For some common weir and flume types. PMD dimensions (P602) are entered directly.
BS-3680 / ISO 1438/1 Thin plate V notch weir on page 73
BS-3680 / ISO 4359 Rectangular Flume on page 74
Palmer Bowlus Flume on page 75
H Flume on page 76
2.
Exponential (P600 = 1)
For most other weir and flume types. PMD exponents provided by the manufacturer are
entered. Flow is calculated using the exponent (P601) and the maximum values (P603 and
P604).
Standard Weirs on page 77
Parshall Flume on page 78
Leoplod Lagco on page 79
Cut Throat Flume on page 80
3.
Universal (P600 = 4,5)
For all other PMDs, the head-to-flow curve can be plotted based on known breakpoints,
usually supplied by the PMD manufacturer.
Typical Flow Characterization on page 81
Example Flumes on page 82
Example Weirs on page 82

Common Parameters

These Quick Start parameters are required for all installations.
Parameter
P001
P002
P003
P004
P005
P006
P007
P801
7ML19985FC03
Index
Value Description
G
6
G
1
G
2
G
102
G
1
G
1.8
G
1.0
G
0.8
HydroRanger 200 – INSTRUCTION MANUAL
Operation
Material
Max. Process Speed
Transducer
Units
Empty
Span
Range Extension to avoid LOE
= OCM
= liquid
= medium
= XPS-10
= meters
= 1.8m
= 1.4m
Page 71