Transducers
Warning: Hazardous voltage present on transducer terminals during
operation.
Run the transducer cable in a grounded metal conduit, separate from other
wiring (except TS-3 temperature sensor wiring, if applicable).
Notes:
•
Do not use coaxial cable because of electrical noise interference
•
Do not connect the shield and white transducer wires together; wire to separate
terminals
•
Disregard older transducer manuals that recommend these practices
A 0.1 µF (100V or greater) capacitor is included with the HydroRanger 200 for retrofitting
old HydroRanger installations. Please see
HydroRanger Installations)
Relays
Relay contacts are shown in the de-energized position. All relays are handled identically
and can be configured as positive or negative logic using P118.
Relay Ratings
•
four Form A, NO
relays(1,2,4,5)
•
two Form C, NO or
NC relays (3,6)
•
5A at 250Vac, non-
inductive
7ML19985FC03
on page 247.
HydroRanger 200 – INSTRUCTION MANUAL
white
TRANSDUCER TWO
black
white
TRANSDUCER ONE
black
HydroRanger 200 Installation (for retrofitting
Power Failure
Relays 1, 2, 4, and 5 are
RELAY 1
normally open and will fail
in the normal state.
RELAY 2
Relays 3 and 6 can be
wired either normally open
or normally closed, and
RELAY 3
will fail in their de-
energized states.
RELAY 4
RELAY 5
RELAY 6