P603 Maximum Head [6 relay model]
The level value associated with Maximum Flow, in Units (P005).
Primary Index
Values
Altered By
Related
This represents the highest head level supported by the PMD and works in conjunction
with Maximum Flow (P604) to define the highest point in the exponential curve. Use it
when the Primary Measuring Device (PMD) requires a maximum head and flow
reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume, and
Universal breakpoints.
P604 Maximum Flow [6 relay model]
The maximum flowrate associated with Maximum Head (P603).
Primary Index
Values
Altered By
Related
This represents the flow at the highest head level supported by the PMD. and works in
conjunction with Maximum Head (P603) to define the highest point in the exponential
curve. Use it when the Primary Measuring Device (PMD) requires a maximum head and
flow reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume,
and Universal breakpoints.
Also use this parameter with Time Units (P606) to define the flowrate units. The limitation
of four digits is for the LCD only, and the flowrate value is available with greater precision
through communications.
Page 168
Single Point Model
Global
Range: -999 to 9999
Preset: Span (P007) value
•
P005 Units
•
P600 Primary Measuring Device
•
P604 Maximum Flow
•
P605 Zero Head
Single Point Model
Global
Range: -999 to 9999
Preset: 1000
•
P600 Primary Measuring Device
•
P603 Maximum Head
•
P606 Time Units
•
P925 Flow Measurement
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
Dual Point Model
Transducer
7ML19985FC03