Enter the Point Number the mA output is based on. This value depends on whether mA
function (P201) is set as transducer or mA input.
For a single point device, if P201 uses a transducer, parameter P202 can only be altered if
P001 (Operation) is set for DPD or DPA.
P202 can be set to a particular point or range of points. When set to a range of points, the
mA output will be the average of the readings from all in service transducers in the range.
Out of service transducers will be ignored.
If P202 mA Output Allocation End contains the value 0, then only 1 transducer has been
assigned to the mA output.
P203 mA Output Value / Transducer
Displays current mA output value for the Point Number.
Primary Index
Values
This displays as an Auxiliary Reading when
does not include adjustments made using Trim features (P214 / P215).
P203 holds the mA value associated with a transducer. This value is used for run mode
display of the mA output. When only one mA output is associated with a transducer, this
parameter holds the value of that mA output. When more than one transducer is
associated with a mA output (set via P202), P203 holds the mA output calculated from the
resulting average of the associated transducer readings. When more than one mA output
is associated with a transducer, P203 holds the value of the first mA output associated
with the transducer.
This parameter is applicable only if any mA output has the transducer
Note:
Point Number as its input source (see P201 and P202).
7ML19985FC03
Level
Range: 0.000 to 22.00 (view only)
HydroRanger 200 – INSTRUCTION MANUAL
key is pressed in the RUN mode and
Page 147