HydroRanger 200 [1 or 3 relay model]
Control
OFF
Level
General
Loss of Echo (LOE)
Cable Fault
Fixed Duty Assist
Pump
Alternate Duty
Assist
Communication
1.
When reading and setting this parameter through Modbus or SmartLinx
communications the parameter values are mapped to different numbers.
HydroRanger 200 Communications
See
tion or the relevant SmartLinx
HydroRanger 200 [6 relay model]
Control
Off
Level
In Bounds
Out of Bounds
General
Rate of Change
Temperature
Loss of Echo (LOE)
Cable Fault
Totalizer
Flow
Flow Sampler
Page 134
Values For P111
1
Type
#
0* Relay set off, no action (preset)
1 Based on level setpoints ON and OFF
6 When echo is lost
7 When the circuit to a transducer is opened
At fixed ON and OFF setpoints and allows multiple
50
pumps to run
At rotating ON and OFF setpoints and allows multiple
52
pumps to run
Based on input from external communications. See
Communications
65
ence.
®
Values For P111
1
Type
#
0* Relay set off, no action (preset)
1 Based on level setpoints ON and OFF
When level enters the range between ON and OFF
2
setpoints
When level exits the range between ON and OFF set-
3
points
4 Based on rate setpoints ON and OFF
5 Based on temperature setpoints ON and OFF
6 When echo is lost
7 When the circuit to a transducer is opened
40 Every 10
41 Every y x 10
HydroRanger 200 – INSTRUCTION MANUAL
Relay Control
section on page 87 for further refer-
on page 87 for Modbus informa-
manual.
Relay Control
y
units (P641-P645)
Z
units (P641-P645) or time duration (P115)
7ML19985FC03