mA I/O

To integrate the HydroRanger 200 with other equipment, use the mA input and outputs.
When a mA input parameter is accessed, a mA symbol appears in the
Note:
upper left corner of the LCD display.
The mA input can be used as a level measurement or can be passed on to a SCADA
system.

mA Input [6 relay model]

Level Reading Parameters
Parameter
P004
P250
P251
P252
P253
To pass the mA input on to a SCADA system, read the value from the appropriate
communication registers. For more information, go to the
Communications

mA Output

The HydroRanger 200 has two mA outputs, used to send measurements to other devices.
Configuring the mA output to send a 4 to 20 mA signal scaled from 10% to 90% of span of
the second transducer:
Parameter
P200
P201
P202
P210
P211
P219
1.
If the level reading drops below 10% of span, the mA output drops below
4 mA.
2.
If the level reading rises above 90% of span, the mA output rises above
20 mA.
7ML19985FC03
Index
Value
1
250
1
2
1
0
1
100
1
0
on page 87.
Index
Value Description
1
2
1
1
1
2
1
10
1
90
1
0
HydroRanger 200 – INSTRUCTION MANUAL
Description
Transducer = mA input 1
Scale = 4 to 20 mA
4 mA = 0% of span
20 mA = 100% of span
Do not damp the input signal
HydroRanger 200
set to 4 to 20 range
send mA proportional to level reading
base mA on level point 2
set 4 mA at 10% of span
set 20 mA at 90% of span
set failsafe action as 0 mA
1
2
Page 47