Siemens HydroRanger 200 Instruction Manual page 17

Table of Contents

Advertisement

Cable
• Do not use coaxial cable for transducer (see General Appendix F: Upgrading on
page 246 for more information)
• transducer and mA output signal to be 2 copper conductors, twisted with shield/drain
wire, 300 Vrms, 0.324 - 0.823 mm
adjacent conductors @ 1kHz = 62.3 pF/m (19 pF/ft). Nominal capacitance between
conductor and shield @ 1kHz = 108.3 pF/m (33 pF/ft) (Belden®
• 365 m maximum
The HydroRanger 200 is to be used only in the manner outlined in this
Note:
instruction manual or protection provided by the equipment may be impaired.
1.
Belden is a registered trademark of Belden Wire & Cable Company.
7ML19985FC03
2
(22 - 18 AWG), nominal capacitance between
HydroRanger 200 – INSTRUCTION MANUAL
1
8760 is acceptable)
Page 7