HydroRanger to HydroRanger 200 Parameters

The HydroRanger 200 uses the current Siemens Milltronics standard parameter set
which is different than the parameter numbers used in the HydroRanger.
The HydroRanger parameters numbers are sequential (P-0 to P-99). The HydroRanger 200
parameters number are also sequential; however, some of the parameters are indexed.
Parameters are indexed when they apply to more than one input or output. The index
value defines the input/output for that parameter. Indexed parameters contain a value for
each index, even if that index is not used.
Example
In the HydroRanger each relay had a dedicated parameter number for its function, ON
and OFF points.
HydroRanger Relay One
P-8: Function
P-9 : ON setpoint
P-10: OFF setpoint
HydroRanger 200 uses P111 for all relays and indexes these parameters.
P-111: Function
P-112: ON
P-113: OFF
The following tables show the differences between the HydroRanger and the
HydroRanger 200. They each show one relay programmed as a high alarm, and two
relays programmed for pump control with alternating pump starts:
HydroRanger
Relay
Parameter
1
P-8 (relay function)
1
P-9 (ON setpoint)
1
P10 (OFF setpoint)
2
P-11 (relay function) 9
2
P-12 (ON setpoint)
2
P-13 (OFF setpoint)
3
P-14 (relay function) 9
3
P-15 (ON setpoint)
3
P-16 (OFF setpoint)
Page 248
Value
1 (alarm)
4 m
3.5 m
3.2 m
0.5 m
3.4 m
0.6 m
HydroRanger 200 – INSTRUCTION MANUAL
HydroRanger 200
Relay
Parameter
1
P111 [1] (relay function) 1
1
P112 [1] (ON setpoint)
1
P113[1] (OFF setpoint)
2
P111[2] (relay function)
2
P112[2] (ON setpoint)
2
P113[2] (OFF setpoint)
3
P111[3] (relay function)
3
P112[3] (ON setpoint)
3
P113[3] (OFF setpoint)
Value
4 m
3.5 m
52
3.2 m
0.5 m
52
3.4 m
0.6 m
7ML19985FC03