P703 Emptying Indicator
The empty rate required to activate the LCD Emptying indicator ( ).
Primary Index
Values
Altered by
Related
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Empty Rate (P701).
P704 Rate Filter
Damps Rate Value (P707) fluctuations.
Primary Index
Values
Alters
Altered by
Related
Enter the time or distance interval over which the Rate Value is to be calculated before
the display updates.
This is automatically altered along with Maximum Process Speed (P003).
This value automatically alters the Rate Update Time (P705) and / or Rate Update
Distance (P706). Alternatively, these parameter values may be altered independently.
7ML19985FC03
Single Point Model
Global
Range: 0.000 to 99.00 m (or equivalent depending on units)
P003 Maximum Process Speed
P005 Units
P007 Span
P701 Max Empty Rate
Single Point Model
Global
0
Rate display not required
Filtered Output
1
Continuously filtered and updated
Interval Output
2
1 minute or 50 mm (2 in)
3
5 minutes or 100 mm (3.9 in)
4
10 minutes or 300 mm (11.8 in)
5
10 minutes or 1000 mm (39.4 in)
P707 Rate Value
P003 Maximum Process Speed
P705 Rate Update Time/ P706 Rate Update Distance
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
Dual Point Model
Transducer
Page 185