Setting The Common Parameters; Set Relay 1 (Operate Rake); Set Relays 2 To 4 (Level Alarms) - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Setting the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter
P001
P002
P003
P004
P005
P006
P007

Set Relay 1 (Operate Rake)

Parameter
P110
P111
P112
P113

Set Relays 2 to 4 (Level Alarms)

P110
P110
P111
P112
P113
P110
P111
P112
P113
P110
P111
P112
P113
Page 68
Index
Value Description
G
4
Operation
G
1
Material
1,2
2
Max. Process Speed
1,2
102
Transducer
G
1
Units
1
1.8
Empty
2
2.2
Empty
1
1.4
Span
2
1.4
Span
3
1.4
Max Differential
Index
Value Description
1
3
Starts the rake when the difference between the
1
50
two levels rises above 0.4 m and stop the rake
1
0.4
when the difference falls below 0.1 m.
1
0.1
2
1
2
1
2
1
2
1.3
2
1.2
3
2
3
1
3
0.2
3
0.4
4
3
4
1
4
1.0
4
0.9
HydroRanger 200 – INSTRUCTION MANUAL
= Differential
= liquid
= medium
= XPS-10
= meters
= 1.8 m
= 2.2 m
= 1.4 m
= 1.4 m
= 1.4 m
Description
Sets Relay Two as a high level alarm for
Transducer One with an ON setpoint of 1.3 m
and an OFF setpoint of 1.2 m.
Sets Relay Three as a low level alarm for
Transducer Two with an ON setpoint of 0.2
m and an OFF setpoint of 0.4 m.
Sets Relay Four as a rake failure alarm as it
uses the differential level point (3) with an
ON setpoint of 1.0 m and an OFF setpoint of
0.9 m.
7ML19985FC03