Transducer Scanning (P726 To P729) - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

The Echo Lock Window is a distance window (units P005) centred on the echo and used
to derive the Reading. When a new measurement is in the window, it is re-centred and
the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock
(P711) before the reading is updated.
When 0 is entered the window is automatically calculated after each measurement. For
slower P003 Maximum Process Speed values the window is narrow, for faster P003
values the window becomes wider.

Transducer Scanning (P726 to P729)

P726 Level System Sync
Enables the System Sync on the terminal block.
Primary Index
Values
Use this if another level measurement system is mounted nearby, and they are wired
together on the Sync terminal.
P727 Scan Delay
The delay, in seconds, between measurements from transducer points (dual point model
only).
Primary Index
Values
Altered by
Related
This feature may only be used to adjust the delay before the next point is scanned. Enter
the amount of delay in seconds. This value is automatically altered when Maximum
Process Speed (P003) is altered.
Page 190
Global
0
not required
1
*
synchronize level monitors
Global
Range: 0 to 60 seconds
Preset: 5.0
P003 Maximum Process Speed