P801 Range Extension
Allows the material level to fall below the Empty setting without reporting LOE.
Primary Index
Values
Related
This feature is useful in OCM applications where the Empty level is set to the bottom of
the weir, and above the bottom of the channel, and should be used if the surface
monitored can fall past the Empty (P006) level in normal operation. The value is added to
Empty (P006) and can be greater than the range of the transducer. If the surface
monitored can extend beyond Empty (P006), increase Range Extension (in Units (P005) or
% of Span) such that Empty plus Range Extension is greater than the transducer face to
furthest surface to be monitored distance. This is often the case with OCM when using
weirs and some flumes.
P802 Transducer with Submergence Shield
Used when the transducer is expected to be submerged on occasion.
Primary Index
Values
Related
When a transducer with a submergence shield is submerged, the shield traps an air
pocket that creates a special echo. The HydroRanger 200 recognizes the echo and
advances the reading to the highest level and operates displays and outputs accordingly.
This feature is effective for when power is returned while the transducer is submerged.
Page 200
Single Point Model
Global
Range: 0.000 to 99.00 m, or max. span (P007), or equivalent
depending on units
Preset: 20% of Span (P007)
P005 Units
P006 Empty
P007 Span
P004 Transducer
Single Point Model
Global
0
*
Off
1
Submergence transducer
P006 Empty
P071 Failsafe Material Level
Relays
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
Dual Point Model
Transducer
7ML19985FC03