Word Order (R40,062); Map Id (R40,063) - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Type
Description
Point
Temperature (2)
Data
Totalizer for points 1
and 2 [6 relay
model]
Discrete Inputs (2)
Relay Outputs (all
I/O
models)
mA Input (1)
[6 relay model]
mA Output (2)
Pump on Setpoint
(all models)
Pump off Setpoint
Pump
(all models)
Control
Pumped Volume (2)
[6 relay model]
Pump Hours (all
models)
Pump Starts (all
models)
Parameter Access
1.
Maximum registers shown; fewer may be used depending on options installed.
The HydroRanger 200 was designed to make it easy for master devices to get useful
information via Modbus. This chart gives an overview of the different sections. A more
detailed explanation of each section follows below.

Word Order (R40,062)

This determines the format of unsigned, double-register integers (UINT32).
0 indicates that the most significant word (MSW) is given first
1 indicates that the least significant word (LSW) is given first
Unsigned Double Precision Integer (UINT32)
See
Additional information is available from our Web site at www.siemens.com/
Note:
processautomation

Map ID (R40,063)

This value identifies the register map used by the HydroRanger 200. See
Index Location
on page 94.
Parameter Access (R43,998 – R46,999)
See also
Page 96
Start
41,030
41,040
41,070
41,080
41,090
41,110
41,420
41,430
41,440
41,450
41,470
43,998 to 46999
HydroRanger 200 – INSTRUCTION MANUAL
1
Data Type
#R
–50 to 150
2
UINT32
4
Bit Mapped
1
Bit Mapped
1
0000 to
1
20,000
0000 to
2
20,000
0000 to
6
10,000
0000 to
6
10,000
UINT32
4
UINT32
12
0000 to
6
10,000
on page 105 for more information.
on page 100 for details.
Read/
Write
R
R/W
R
R/W
R
R/W
R/W
R/W
R
R
R
R/W
P782 Parameter