Control Functions (P111)
Each relay can be configured independently to take advantage of the HydroRanger's
advanced features and flexibility. Start with a preset application and then change the
required parameters to make the task more efficient.
Setpoints (P112, P113)
Each relay is triggered by one or more setpoints. The setpoints can be based on absolute
level (P112, P113) or rate of change (P702, P703). Each control function specifies which
setpoints are required.
P100 Preset Applications [6 relay model]
Six preset applications to configure or bench test the unit.
Primary Index
Values
Alters
Related
Select an application that is similar to yours and change the parameters required. If none
suit, then refer to P111 Relay Control Function on page 133.
Programming the relays independently is the most common method used.
Note:
Page 132
Global
0
* OFF
1
Wet Well 1
2
Wet Well 2
3
Reservoir 1
4
Reservoir 2
5
Screen
6
Alarms
•
P110 Level Source
•
P111 Relay Control Function
•
P112 Relay On Setpoint
•
P113 Relay OFF Setpoint
•
P121 Pump by Rate
•
P001 Operation
HydroRanger 200 – INSTRUCTION MANUAL