With P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112 < P113).
This shows a high alarm:
Parameter
P111
P112
P113
P110
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by P660.

Loss of Echo (LOE)

Parameter
P110
P111
P070
7ML19985FC03
Index
Value
5
5
5
45
5
43
5
1
Index
Value
5
1
5
6
G
0.5
HydroRanger 200 – INSTRUCTION MANUAL
Description
Alarm on temperature
ON setpoint at 45 °C
OFF setpoint at 43 °C
Take the temperature reading from
Transducer One
Description
Alarm on LOE for Transducer One
Alarm on LOE
Trip alarm when 0.5 minutes (30 seconds)
pass without detecting a valid echo.