Communications Installation

Wiring Guidelines

the RJ-11 cable maximum length is 3 meters
RS-485 maximum length is 1,200 meters (4,000 feet)
use 24 AWG (minimum)
use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-485 for port 2 (Belden 9842)
run the communication cable separately from power and control cables (do not tie
wrap your RS-232 or RS-485 cable to the power cable or have them in the same
conduit)
use shielded cable and connect to ground at one end only
follow proper grounding guidelines for all devices on the bus
Improper wiring and incorrect choice of cables are two of the most
Note:
common causes of communication problems.

Ports 1 and 2

Port
Wall Mount
1
RS-232 port (RJ-11 modular telephone jack) is on the motherboard and
is generally used with a laptop computer or modem.
2
Connections for the RS-485 port are on the terminal block.

Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locations

The RJ-11 jack and the RS-485 port are inside the enclosure of the unit.
TB2
2
1
RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
Page 90
TB1
L2/N L1
TB3
SYNC
mA INPUT
SHIELD
1
4 - 20 mA
OUTPUTS
2
TS-3
SHIELD
1
2
DISCRETE
INPUTS
COM
RS485
A
B
HydroRanger 200 – INSTRUCTION MANUAL
RJ-11 Jack
RS-485 Port
7ML19985FC03