In Bounds/ Out Of Bounds Range [6 Relay Model]; Temperature Alarm; Cable Fault; Temperature [6 Relay Model] - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

In Bounds/ Out of Bounds Range [6 relay model]

Use the bounded range alarms to detect when the level is inside or outside of the range.
By using a bounded range alarm, you can effectively put two level alarms (high and low)
on one relay.
Setting an Out of Bounds Alarm
Parameter
P111
P112
P113
P116
Results:
Trips alarm above 1.35 m and below 0.25m
Resets alarm below 1.25 m and above 0.35m
Setting an In Bounds Alarm
Parameter
P111
P112
P113
P116
Results:
Trips alarm below 1.25 m and above 0.35 m
Resets alarm above 1.35 m and below 0.25 m

Cable Fault

Activates an alarm if transducer cable circuit enters a shorted or opened state.
Parameter
P111
P110

Temperature [6 relay model]

Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112
and P113).
Page 54
Index
Value
5
3
5
1.3
5
0.3
5
0.05
Index
Value
5
2
5
1.3
5
0.3
5
0.05
Index
Value
5
7
5
1
HydroRanger 200 – INSTRUCTION MANUAL
Description
Alarm on transducer cable fault
Alarm on Transducer One
7ML19985FC03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents