In Bounds/ Out of Bounds Range [6 relay model]
Use the bounded range alarms to detect when the level is inside or outside of the range.
By using a bounded range alarm, you can effectively put two level alarms (high and low)
on one relay.
Setting an Out of Bounds Alarm
Parameter
P111
P112
P113
P116
Results:
•
Trips alarm above 1.35 m and below 0.25m
•
Resets alarm below 1.25 m and above 0.35m
Setting an In Bounds Alarm
Parameter
P111
P112
P113
P116
Results:
•
Trips alarm below 1.25 m and above 0.35 m
•
Resets alarm above 1.35 m and below 0.25 m
Cable Fault
Activates an alarm if transducer cable circuit enters a shorted or opened state.
Parameter
P111
P110
Temperature [6 relay model]
Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112
and P113).
Page 54
Index
Value
5
3
5
1.3
5
0.3
5
0.05
Index
Value
5
2
5
1.3
5
0.3
5
0.05
Index
Value
5
7
5
1
HydroRanger 200 – INSTRUCTION MANUAL
Description
Alarm on transducer cable fault
Alarm on Transducer One
7ML19985FC03