Average or Differential [6 relay model]

For differential or average operation with a single-point HydroRanger 200, set P001 to 4
(differential) or 5 (average) and connect two transducers of the same type. All of the
relevant parameters then become indexed by the correct transducer:
Index
2
3

Dual Point Models

The HydroRanger 200 starts in an OFF state and does not take level measurements. For
measurement setup, configure these basic parameters:
If the application uses two measurement points, provide the basic information for each
measurement point separately:
Parameter
P001
P002
P003
P004
P005
P006
P007
Average or Differential [6 relay model]
For differential or average operation dual-point HydroRanger 200, set P001 to 4
(differential) or 5 (average) and connect two
transducers of the same type.
7ML19985FC03
Description
indexed by Transducer One or Two
indexed by level measurement
1 = Transducer One
2 = Transducer Two
3 = Calculated Level (average or difference)
Index
Value Description
1
1
2
3
1
1
2
1
1
2
2
3
1
104
2
102
G
1
1
12
2
4
1
11
2
3.5
HydroRanger 200 – INSTRUCTION MANUAL
Operation = level
Operation = distance
Material = Liquid
Max. Process Speed = medium
Max. Process Speed = fast
Transducer = XPS - 15
Transducer = XPS - 10
Units = meters
Empty = 12m
Empty = 4m
Span = 11m
Span = 3.5m
3
Relay Number
Ring indicates
relay is configured
Dot indicates
relay is energized/
de-energized
Page 37