P215 20 mA Output Trim
Calibrates the 20 mA output.
Primary Index
Values
Related
Adjust this value so the device indicates 20.00 mA when P215 is accessed.

mA Output Failsafe (P219) [6 relay model]

Please note that this parameter applies to the HydroRanger 200 6 relay model only.
P219 mA Output Failsafe [6 relay model]
Use for failsafe operation, independent of the Failsafe Material Level (P071).
Primary Index
Values
Related
Selecting an independent mA Failsafe option:
1.
Press MODE
2.
Press ARROWS
3.
Press ENTER
Or, to produce an mA output at a specific value, enter the value required. This is used only
if mA output is allocated to a transducer (P201 = 1 to 7).

mA Input (P250 to P260) [6 relay model]

Please note that these parameters apply to the HydroRanger 200 6 relay model only.
Page 150
mA output
Preset: 20.00
P214 4mA Output Trim
mA output
Range: 0.000 to 22.00
OFF
*
mA output responds to Failsafe Material Level (P071).
last known value is held until normal operation
HOLd
resumes
LO
produce the Empty mA output immediately
HI
produce the Span mA output immediately
P201 mA Output Function
to display the Auxiliary Function symbol.
to scroll access the failsafe options.
when the desired option displayed.
HydroRanger 200 – INSTRUCTION MANUAL