Product ID (R40,064)

This value identifies the Siemens device type:
Device Type
HydroRanger 200 [1 or 3 relay model]
HydroRanger 200 [6 relay model]
Point Data (R41,010 – R41,031)
Measurement point data contain the current instrument readings. These are the values
shown for the reading measurement for each measurement point. The reading is based
on the setting for P001 (operation). P001 can be set to level, distance, OCM flow, or
Parameter Reference
volume. See
The measurement registers are 41,010 to 41,012. The HydroRanger 200 uses 41,010 when
configured with a single transducer and 41,010 to 41,012 when configured with two
transducers (P111=4 or 5 only). Two transducers can create three readings because they
can generate an average or differential reading (R41,012) as well as the two level
readings (R41,010 and R41,011).
Available registers:
Data
Reading
Volume [6 relay
model]
Temperature
The reading is expressed as a percentage of full scale, multiplied by 100:
Reading
0
5000
7564
20,000
Totalizer (R41,040 – R41,043)
The totalizers are stored as 32 bit integers using two registers. The totalizers can be read
with R41,040 and R41,041 as totalizer for Point 1, and R41,042 and R41,043 as totalizer for
Point 2. The totalizer values can be reset to any value by writing that value to the
registers. The values can be cleared by writing zero (0) to the registers.
7ML19985FC03
section on page 115 for details.
Registers
41,010 to 41,012
41,020, 41,021
41,030 and 41,031
Value
0.00%
50.00%
75.64%
200.00%
HydroRanger 200 – INSTRUCTION MANUAL
Value
6
4
Parameter
P920
P924
P912
Page 97