Set Relays to FIXED DUTY BACKUP [6 relay model]
Parameter
P111
P111
P111
Set the Relay ON Setpoints [6 relay model]
Parameter
P112
P112
P112
Set the Relay OFF Setpoints [6 relay model]
Parameter
P113
Set Relays to ALTERNATE DUTY SERVICE [6 relay model]
Parameter
P111
P111
P111
P122
P122
P122
Set the Relay ON Setpoints [6 relay model]
Parameter
P112
P112
P112
Set the Relay OFF Setpoints [6 relay model]
Parameter
P113
Page 60
Index
Value Description
1
51
2
51
3
51
Index
Value Description
1
0.4m
2
0.3m
3
0.2m
Index
Value Description
0
1.3m
Index
Value Description
1
54
2
54
3
54
1
25
2
50
3
25
Index
Value Description
1
0.4m
2
0.3m
3
0.2m
Index
Value Description
0
1.3m
HydroRanger 200 – INSTRUCTION MANUAL
Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY BACKUP . Only one pump will
ever run at one time.
Sets the three setpoints for the pump relays.
The setpoints remain attached to the pump
relays.
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Sets the pump relays (index 1, 2, and 3) to
SERVICE RATIO DUTY ASSIST
Sets the ratio to: 25% – Pump One
50% – Pump Two
25% – Pump Three
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
7ML19985FC03