Siemens HydroRanger 200 Instruction Manual page 15

Table of Contents

Advertisement

Fixed
• 0. 1 7 % per °C deviation from programmed value
Outputs
Transducer drive
• 315 V peak
mA Analog
HydroRanger 200 (all models):
Single or Dual point versions include two mA outputs
• 0-20 mA
• 4-20 mA
• 750 ohm maximum
• Resolution of 0.1%
• Isolated
1
Relays
• One:
1 control
• Three:
2 control
1 alarm control
• Six:
4 control
2 alarm control
• All relays rated 5A at 250 V AC, non-inductive
Control Relays
• 1, 2 or 4 Form A, NO relays (numbers 1, 2, 4, 5)
Alarm Relay
• 0, 1 or 2 Form C, NO, or NC relay (numbers 3, 6)
Communication
• RS-232 running Modbus RTU and ASCII via RJ-11 connector
• RS-485 running Modbus RTU and ASCII via terminal blocks
Optional
®
• SmartLinx
compatible
1.
All relays are certified only for use with equipment that fails in a state at or
under the rated maximums of the relays.
7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 5