Mounting The Enclosure - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Panel Mount Dimensions
278 mm
(10.93")

Mounting the Enclosure

Once cutout is complete and mounting holes are drilled, follow these steps:
1.
Remove lid from unit by undoing the six lid screws and lifting it off its hinges.
2.
Remove the four screws holding the motherboard to the enclosure.
3.
Be careful not to damage the electronics with static electricity. Remove the
motherboard from the enclosure by pulling the board straight out.
4.
Drill the required cable entry holes. Be sure to compensate for panel door
dimensions and make sure conduit holes do not interfere with the lower areas on
the terminal block, circuit board, or SmartLinx card.
5.
Replace board and fasten the four screws.
6.
Place the unit into the panel and insert hexagonal fasteners through bevel slots and
predrilled panel holes.
7.
Fasten with wingnuts and hand tighten.
8.
Add conduit or glands and wire as required, then replace the lid.
Helpful hint:
Use tape to hold hexagonal heads in slots while attaching wingnuts.
Page 12
198 mm
(7.80")
HydroRanger 200 – INSTRUCTION MANUAL
97 mm
(3.82")
36 mm
(1.40")
7ML19985FC03

Hide quick links: