P633 LCD Totalized Decimal Position [6 relay model]
Enter the maximum number of decimal places to be displayed.
Primary Index
Values
Related
Set the decimal position during initial commissioning of the HydroRanger
Note:
200. If the position is changed later, the totalizer data in P322 and P323 will be
incorrect and must be reset according to the new decimal value.
In RUN mode, the number of decimal places displayed is not automatically adjusted.
When the LCD Total value is so large as to exceed display capabilities, the total rolls over
to 0 and continues incrementing.
P640 Remote Totalized Multiplier [6 relay model]
Use this feature if the remote totalizer (device connected to the relay set for totalizer
operation [relay Function, P111 = 40]), updates too slowly or rapidly.
Primary Index
Values
Values
Related
Parameter is relevant only if Operation is set to OCM or Pumped Volume (P001 = 6 or 7).
The relays on the HydroRanger 200 have a maximum frequency of 2.5 Hz.
Page 176
Single Point Model
Global
0
no digits after the decimal point
1
1 digit after the decimal point
2
2 digits after the decimal point
*
3
3 digits after the decimal point
LCD Totalizer (P322 and P323)
Single Point Model
Global
-3
.001
-2
.01
-1
.1
0
*
1
1
10
2
100
3
1000
4
10,000
5
100,000
6
1,000,000
7
10,000,000
P001 Operation
P111 Relay Control Function
P114 Relay Duration Setpoint
P115 Relay Interval Setpoint
P645 Relay Duration
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
Dual Point Model
Transducer