Activating The Hydroranger 200; Changing Parameters - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Activating the HydroRanger 200

All the instructions in the following procedures apply to the hand programmer and
assume that the HydroRanger 200 is activated.
1.
Power the HydroRanger 200.
2.
Point the programmer at the unit and press PROGRAM
3.
Press DISPLAY
Power up display
Note:
Single Point Model
preset to display distance from the face of the transducer to the
material
transducer selection is preset for the XPS-10
empty distance is preset to 5m
Dual Point Model
starts in an OFF state and does not take level measurements
to set up measurement, the quick start parameters must be
configured
See

Changing Parameters

If Parameter Value alteration is not permitted, access the Lock parameter
Note:
(P000) and enter the security code, (see Security below).
1.
Starting in RUN mode, press PROGRAM
unit into PROGRAM mode.
2.
Press DISPLAY
3.
Enter the Parameter Number (e.g. 110). After the third digit is entered, the parameter
value is shown.
4.
Enter the new value, and press ENTER
value, either accepting or replacing it with a valid value.
Helpful Hints
For parameters P001 to P009, press a single digit (1–9) and then press DISPLAY
to show that parameter.
The ? icon indicates that the HydroRanger 200 has accepted the value but that it
conflicts with other values entered. Double-check your programming.
By default, the SCROLL arrows
any that have been changed.
P733 sets all parameters to be scroll-accessed.
7ML19985FC03
.
Quick Start (P001 to P007)
to select the Parameter Number field.
HydroRanger 200 – INSTRUCTION MANUAL
.
on page 117
and then press DISPLAY
. The HydroRanger 200 interprets the
show only the Quick Start parameters and
to put the
Page 31