Siemens HydroRanger 200 Instruction Manual page 156

Table of Contents

Advertisement

HydroRanger 200 [6 relay model]
Primary Index
Values
Related
Altered By
P202 mA Output Allocation
Sets the input source from which the mA output is calculated.
Please note that parameter P202 values vary between the HydroRanger 200, 1 or 3 relay
model, and the HydroRanger 200, 6 relay model.
HydroRanger 200 [1 or 3 relay model]
Primary Index
Values
Related
HydroRanger 200 [6 relay model]
Primary Index
Values
Related
Page 146
mA output
value
mA function
0
OFF
1
level
2
space
3
distance
4
volume
5
flow
6
head
7
volume rate
8
mA input
9
comms input
P202 mA Output Allocation
P911 mA Output Value
P001 Operation
mA output
1
*
Point 1
P201 mA Output Function
mA output
1
*
Point 1
2
Point 2
1:2
Average of readings from Point 1 and Point 2
3
Point 3
P201 mA Output Function
HydroRanger 200 – INSTRUCTION MANUAL
Operation (P001)
level, differential, or average
space
distance
level or space
OCM
7ML19985FC03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents