Volume [6 relay model]

Volume is a feature of the HydroRanger 200 6 relay model. Volume is used in two
situations:
1.
Calculate and display volume instead of level. For programming all setpoint
parameters in terms of volume units rather than level units.
2.
Calculate pumped volume to accomplish the following:
Totalize the volume of material that is pumped out of the wet well
Set an alarm on pump efficiency
If you require this functionality, please contact your local Siemens Milltronics
representative at www.siemens.com/processautomation .

Readings

When using volume, readings are given in arbitrary units specified in P051.
The default is 100, which gives a reading in percent of total. Use whatever units you want
here. If the value is too large for the four-digit LCD, use a larger unit.
Example
If a wet well has a maximum capacity of 250,000 liters, use the value 250.0 for P051 and
set the reading in 1000s of liters.

Tank Shape and Dimensions

There are many common tank shapes to select from. (See P050. If possible, use one of
these.) Each tank shape uses the Empty distance (P006) in its calculations of volume.
Some tank shapes also require extra dimensions to calculate the volumes. Do not
estimate these values. They must be correct to ensure the accuracy of your volume
calculations.
Parameter
P050
P051
P052
Notes:
The default reading changes to a range from 0 to 100 (the value in P051)
Empty (P006) is still measured to the bottom of the tank, not the top of A.
7ML19985FC03
To configure volume for a tank with a half-sphere bottom, set the
following:
Index
Value Description
1
4
1
100
1
1.3
HydroRanger 200 – INSTRUCTION MANUAL
selects the correct tank shape
sets maximum volume at 100 (percent)
sets A to 1.3 m
Page 49