P131 Pump Run-On Duration [6 relay model]
Sets the number of seconds that the pump runs on.
Primary Index
Values
Related
Your pump capacity determines the amount of material that can be removed. Choose a
value long enough to clean out the vessel bottom, yet short enough not to run the pump
dry. Also be sure that this value does not overlap with P130 (Interval). The timing should
look something like this:
P131
P132 Pump Start Delay [6 relay model]
Sets the minimum delay (in seconds) between pump starts.
Primary Index
Values
Related
Use this feature to reduce a power surge from all pumps starting at the same time. This
delay determines when the next pump is permitted to start.
P133 Pump Power Resumption Delay [6 relay model]
Sets the minimum delay before the first pump restarts after power failure.
Primary Index
Values
Related
This reduces the surge from the first pump starting immediately on power resumption.
When this delay expires, other pumps will start as per P132.
7ML19985FC03
Relay
Range: 0.0 to 9999
Preset: 0.000
Advanced Pump Control Modifiers (P130 to P136)
P130 (Pump Run-On)
Global
Range: 0.0 to 9999
Preset: 10
Value is divided by 10 in simulation mode.
Advanced Pump Control Modifiers (P130 to P136)
P121 Pump by Rate
Global
Range: 0.000 to 9999
Preset: 10
Advanced Pump Control Modifiers (P130 to P136)
P132 Pump Start Delay
HydroRanger 200 – INSTRUCTION MANUAL
P132
Page 141