P728 Shot Delay
The delay, in seconds, between transducer shots.
Primary Index
Values
Use this if transient acoustic noise within the vessel is causing measurement difficulties
due to echoes from one shot being received on the next. If more than one ultrasonic unit
is installed for redundancy, this value should be 0.
P729 Scan Time
View the elapsed time (in seconds) since the point displayed was last scanned.
Primary Index
Values
Related
This may be viewed as an Auxiliary Reading in the RUN mode.

Display (P730 to P739)

P730 Auxiliary Reading
Use this feature to display operator selected Auxiliary Readings temporarily or
indefinitely (as desired).
Primary Index
Values
Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary
Readings until another Auxiliary Reading is selected or programming mode is entered.
Hand Programmer
See the
Selecting the Auxiliary Reading operation
1.
Press READING
2.
Press ARROWS
3.
Press ENTER
7ML19985FC03
Transducer
Range: 0.1 to 4.0
Preset: 0.5
Level
Range: 0.000 to 9999 (view only)
P001 Operation
Global
Range: 000 to 999
Display: OFF, HOLd
section on page 26 for RUN mode auxiliary readings.
to display the Auxiliary Function symbol.
to access the OFF or HOLd option desired.
HydroRanger 200 – INSTRUCTION MANUAL