Service Ratio Duty Backup (P111 = 55) [6 Relay Model]; First In First Out (Fifo) (P111 = 56) [6 Relay Model]; Pump By Rate (P121) [6 Relay Model]; Other Pump Controls [6 Relay Model] - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Service Ratio Duty Backup (P111 = 55) [6 relay model]

Selects the lead pump based on number of hours each pump has RUN and the specified
ratios that each pump requires. Only one pump can RUN at a time.
Please note that this feature applies to the HydroRanger 200, 6 relay model.
This algorithm is the same as Service Ratio Duty Assist except that it will only RUN one
pump at a time. When the next pump in the sequence starts, the previous pump stops.

First In First Out (FIFO) (P111 = 56) [6 relay model]

Selects the lead pump based on the Alternate duty but uses staggered off setpoints and
shuts down pumps based on the first in, first out rule.
Please note that this feature applies to the HydroRanger 200, 6 relay model.
This algorithm starts pumps in the same way as Alternate Duty Assist but uses staggered
OFF setpoints to shut the pumps down. When the first OFF setpoint is reached the FIFO
rule shuts down the first pump started. If the pumps started in sequence 2,3, 1 then they
would be shut down in sequence 2,3, 1 .

Pump by Rate (P121) [6 relay model]

Starts pumps until the level is changing at the rate specified in P702 or P703.
Please note that this feature applies to the HydroRanger 200, 6 relay model.
Pumping costs can be less because only the highest ON setpoint needs to be
programmed and this results in a lower difference in head to the next wet well which, in
turn, results in less energy being used to pump out the well.

Other Pump Controls [6 relay model]

Please note that these features apply to the HydroRanger 200, 6 relay model.
There are a number of other controls available to modify pump behaviour.
Pump Run-On (P130, P131)
Extends the RUN period for a pump based on a set time interval. This allows for the wet
well to be pumped lower than usual and reduces sludge build-up on the well bottom.
Wall Cling Reduction (P136)
Varies the ON and OFF setpoints to keep a fat ring from forming around the walls of the
wet well.
Pump Group (P137)
Allows for two different Alternate Duty Assist or Alternate Duty Backup pump groups in
the same application.
7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 243

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents