Relay Controlled By Communications; Tracking Pump Usage - Siemens HydroRanger 200 Instruction Manual

Table of Contents

Advertisement

Example:
The flush valve connects to Relay Four and the watched pump is on Relay One.
Parameter
P170
P171
P172
P173

Relay Controlled by Communications

A relay can be controlled directly by a remote system through communications. No other
control schemes can then be used with a relay configured this way. Communications can
be used to force status of some control relays, such as pumps.
Settings:
Parameter
P111

Tracking Pump Usage

You can find out how much an individual pump has been used by viewing the pump
records parameters.
Information Available
Current RUN time
Total pump hours
Total pump starts
Total pump RUN on occurrences
Page 66
Index
Value Description
G
1
G
3
G
10
G
120
Index
Value Description
5
65
HydroRanger 200 – INSTRUCTION MANUAL
Watch Relay One to count pump cycles.
Open the flush valve for 3 cycles.
Use the flush value every 10 cycles.
Open the flush valve for 120 seconds.
Sets Relay Five to communications control.
Parameter Access
P309
P310
P311
P312 [6 relay model ONLY]
7ML19985FC03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents