P712 Echo Lock Sampling
The sampling criterion sets the number of consecutive echoes appearing above or below
the echo currently locked onto, that must occur before the measurements are validated
as the new reading (for Echo Lock P711 values: 1 or 2).
Primary Index
Values
Related
P711 value
1, max verification
2, material agitator
Example:
Setting
•
P711 = 2, material agitator
•
P712 = 5:2
Result
•
a new reading will not be validated unlessfive consecutive measurements higher or
two consecutive measurements lower than the current reading occur
•
Resetting P711 returns P712 to the respective preset values
P713 Echo Lock Window
Adjusts the size of the Echo Lock Window.
Primary Index
Values
Altered by
Related
7ML19985FC03
Single Point Model
Global
Range: 1:1 to 50:50
Format: x:y
x = the number of above echoes
y = the number of below echoes
•
P711 Echo Lock
Single Point Model
Global
Range: 0.000 to 99.00 m (or equivalent depending on units), nearest
acceptable value is returned
Preset: 0.000
•
P003 Maximum Process Speed
•
P005 Units
•
P711 Echo Lock
HydroRanger 200 – INSTRUCTION MANUAL
Dual Point Model
Transducer
P712 preset value
5:5
5:2
Dual Point Model
Transducer
Page 189