Characterization Chart [6 relay model]

If you cannot use a pre-defined tank, then use one of the universal tank shapes and
program the characterization curve.
1.
Plot a volume to height chart. Usually a tank supplier will provide this chart.
However, if you have a custom-built wet well then you will need access to complete
drawings of the well or accurate measurements.
2.
Enter the curve values from this chart into P054 and P055.
3.
Ensure extra points are added around sharp transitions in the wet well volume (e.g:
as steps in the well wall).
The end points in the curve are 0,0 (fixed) and the point defined by P007–
Note:
Span and P051–Maximum Volume.

Example Chart

MAX VOLUME
P051
0,0
Page 50
LEVEL (P054)
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03