Siemens HydroRanger 200 Instruction Manual page 130

Table of Contents

Advertisement

Related
(chart cont' d from
previous page)
P005 Units
Specifies measurement units used for dimensional values.
Primary Index
Values
Alters
Changing this value automatically changes the units displayed for many parameters.
Existing values are converted and do not have to be re-entered.
P006 Empty
Enter distance in units (P005) from the face of the transducer to the process empty point.
Primary Index
Values
Alters
Altered By
Related
Setting this value also sets Span (P007) unless Span was already set to another value.
For distance operation (P001=3), Span is preset to Empty.
Page 120
P203 mA Output Value/Transducer
mA Input (P250 to P260) (related only to Value 250)
P800 Near Blanking
P823 Reform Echo
P832 TVT Shaper Adjust
P840 Short Shot Number
P841 Long Shot Number
P842 Short Shot Frequency
P843 Long Shot Frequency
P844 Short Shot Width
P845 Long Shot Width
P852 Short Shot Range
Global
1
*
Meters
2
Centimeters
3
Millimeters
4
Feet
5
Inches
P006 Empty
P007 Span
P603 Maximum Head
P605 Zero Head
P620 Low Flow Cutoff
P921 Material Measurement
P926 Head Measurement
P927 Distance Measurement
Transducer
Range: 0.000 to 99.000 m (or equivalent depending on units)
Preset: 5.000 m (or equivalent depending on units)
P007 Span
P005 Units
P800 Near Blanking
P921 material Measurement
P927 Distance Measurement