11.2.4 Output 5, analog output (option)
11.2.5 Transducer supply
11.2.6 Interface RS-485 (optional)
11.3 General ratings
54/57
Analog output, electrically isolated from the analog inputs:
DU < AC 30 V , DU < DC 50 V
Standard signals
DC 0...10 V (short-circuit proof)
DC 0...20 mA
DC 4...20 mA
Accuracy: ±0.25 % ±50 ppm / K
DC 24 V, 30 mA (short-circuit proof)
Baud rate:
Protocol:
Unit address:
Galvanic separation between supply voltage, analog inputs and outputs.
ð
Section 4.3 «Galvanic separation»
Weight:
Data backup:
Operating voltage:
Power consumption:
Electrical connection:
Electrical safety:
Case:
CC1B7865en
Load, burden
Load = > 500 W
Burden = < 500 W
Burden = < 500 W
4,800, 9,600 or 19,200
MOD bus
1...99
approx. 430 g
EEPROM
AC 100...240 V ±10 %, 48...63 Hz
approx. 5 VA
at the rear, via plug-in screw terminal strips, angled
at 45°
to EN 60730
mounting depth 130 mm
plastic body with rear panel, self-extinguishing
flammability class: UL94 V0
seal between case and control panel
05.12.2002
11. Technical data
HVAC Products