Before initiating a Quick start wizard to configure the device, you may wish to gather the
necessary parameter values. Parameter configuration charts that list all parameters and
available options for each application type are available on our website.
Go to Product page (www.siemens.com/sitransLT500).
Click "Support > Application examples".
Record data and select from options on the chart that apply to your application, then with
this data on hand, complete the quick start wizards.
6.5

Local commissioning

6.5.1

Wizard order

Procedure
The quick start wizards provide an easy step-by-step procedure to help configure the device
for various applications. We recommend that configuration is done in the following order:
1. First, run the appropriate "Quick commissioning" wizard for your application (Level, Space,
Distance, Volume, Volume flow).
2. Set up pumps (if applicable) via the "Pump control" wizard.
3. Configure control relays (if applicable) via the "Basic control" wizard.
4. Configure alarms (if applicable) via the "Alarm" wizard.
5. Configure totalizers and samplers (if applicable) referencing the respective parameters.
It is important that alarms and other controls are configured last to avoid pump relay
assignments being overridden by the "Quick commissioning" wizard.
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA
Commissioning