Parameters For Initialize Mode; Application Parameters - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Appendices

Parameters for Initialize Mode

Con-
Regis-
Class 64 (hex)
stant
ter num-
In-
ber
stance
(hex)
A1-00
0100
01
A1-01
0101
01
A1-02
0102
01
A1-03
0103
01
A1-04
0104
01
A1-05
0105
01
A2-01
0106 to
01
to
0125
A2-32

Application Parameters

Con-
Regis-
Class 64 (hex)
stant
ter num-
In-
ber
stance
(hex)
b1-01
0180
01
b1-02
0181
01
b1-03
0182
01
b1-04
0183
01
b1-06
0185
01
b1-07
0186
01
b1-08
0187
01
b2-01
0189
01
b2-02
018A
01
b2-03
018B
01
b2-04
018C
01
b3-01
0191
01
b3-02
0192
01
b3-03
0193
01
b3-05
0195
01
b4-01
01A3
01
Name
At-
tribute
00
Language selection for Digital Operator
display
01
Parameter access level
02
Control method selection
03
Initialize
04
Password
05
Password setting
06 to
User-parameter settings
25
Name
At-
tribute
80
Reference selection
81
Operation method selection
82
Stopping method selection
83
Prohibition of reverse operation
85
Read sequence input twice
86
Operation selection after switching to
remote mode
87
Run command selection in program-
ming modes
89
Zero speed level (DC injection braking
starting frequency)
8A
DC injection braking current
8B
DC injection braking time at start
8C
DC Injection braking time at stop
91
Speed search selection (current detec-
tion or speed calculation)
92
Speed search operating current (cur-
rent detection)
93
Speed search deceleration time (cur-
rent detection)
95
Speed search wait time (current detec-
tion or speed calculation)
A3
Timer function ON-delay time
Chapter 10
Setting
Setting
Default
range
unit
setting
0 to 6
1
1
0 to 2
1
2
0 to 2
1
0
0 to 3330 1
0
0 to 9999 1
0
0 to 9999 1
0
0180 to
1
---
050C
Set the
register
numbers
for b1-01
to o2-11.
Setting
Setting
Default
range
unit
setting
0 to 4
1
1
0 to 3
1
1
0 to 3
1
0
0 to 2
1
0
(See
note 6.)
0, 1
1
1
0, 1
1
0
0, 1
1
0
0.0 to
0.1 Hz
0.5
10.0
0 to 100
1%
50
0.00 to
0.01 s
0.00
10.00
0.00 to
0.01 s
0.50
10.00
0 to 3
1
2 (See
note 1.)
0 to 200
1%
120 (See
note 1.)
0.0 to
0.1 s
2.0
10.0
0.0 to
0.1 s
0.2
20.0
0.0 to
0.1 s
0.0
3000.0
(See
note 5.)
Write
during
opera-
tion
Yes
Yes
No
No
No
No
No
Write
during
opera-
tion
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
10-51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3g3rv-pdrt2

Table of Contents