Status Area and Troubleshooting
9-2-4
CQM1H-series Controller Link Units
Status Area
Error Information: IR 190
308
Bit status
Data link table error
(CIO 1500 + 25
n, bit 1)
is 1: ON
Network parameter error
(CIO 1500 + 25
n, bit 0)
is 1: ON
Probable cause
The data link table data in
the EEPROM of the CPU
Unit is damaged.
There is an error in the
data link table settings.
The CPU Unit's EEPROM
data link tables or the net-
work parameters are dam-
aged.
There is an error in the net-
work parameter settings, or
node address of the local
node is larger then the
maximum address set
within the network parame-
ters.
1: Network parameter error (In PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Error log exists
Section 9-2
Probable remedy
Refer to 5-3 Starting and
Stopping Data Links and
reset the data link tables
correctly. If the error occurs
again, replace the CPU
Unit.
When using manually set
data links, refer to 5-3
Starting and Stopping Data
Links and remake and set
the data link tables cor-
rectly. When manually set
data links are not being
used, delete the data link
tables.
Refer to 8-1-3 Network
Parameters and reset the
data correctly. If the error
occurs again, replace the
CPU Unit.
Either set the EEPROM
Clear Bit in the DM Param-
eter Area to ON, or use the
Initialize network parame-
ters operation on the Main-
tenance Menu of the
Controller Link Support
Software to initialize the
network parameters and
then cycle the power sup-
ply.
Refer to 8-1-3 Network
Parameters and reset the
network parameters or the
node address.