Omron 3G3MV-PDRT2 User Manual page 343

Devicenet communications units
Table of Contents

Advertisement

Appendices
Note 1. The setting unit of the frequency reference can be changed in o1-03 (frequency reference
setting and display units). The default setting is 0.01 Hz.
Note 2. The multi-function analog output 1 and 2 registers can be used to set the Inverter's analog
outputs by means of communications. To do that, set "31 (1F hex)" for H4-01 (multi-function
analog output terminal 21 monitor selection) and H4-04 (multi-function analog output termi-
nal 23 monitor selection).
Note 3. The Inverter's multi-function outputs can be turned from ON to OFF by means of communi-
cations. To do that, set "F" for multi-function output parameters H2-01 (multi-function contact
output: terminals 9-10 function selection), H2-02 (multi-function output 1: terminal 25 func-
tion selection), and H2-03 (multi-function output 2: terminal 26 function selection).
10-7-2 Inverter Monitoring Functions
All Inverter monitoring can be accessed. To read Inverter status, fault monitoring, alarm monitoring, I/
O status monitoring, error log, etc., specify the register number from the following table and read the
data.
Class 64
number (hex)
Instance Attribute
00
10
0010
00
11
0011
00
12
0012
---
---
0013
00
14
0014
00
15
0015
00
16
0016
00
17
0017
00
18
0018
00
19
0019
00
1A
001A
---
---
001B to 001F
Inverter Status: Register Number 0010 Hex
Bit
0
During Run
1
Zero speed
2
Forward/reverse (1: Reverse operation)
3
during Fault Reset input
4
Frequency agree 1
5
Inverter operation ready
6
Alarm
7
Fault
8 to 15
Not used.
Register
Function
Inverter status
Operator status
Operator setting error
number
Not used.
Fault 1
Fault 2
Fault 3
CPF error 1
CPF error 2
Alarm 1
Alarm 2
Not used.
Content
Content
(Refer to table below.)
(Refer to table below.)
OPE error number
---
(Refer to table below.)
(Refer to table below.)
(Refer to table below.)
(Refer to table below.)
(Refer to table below.)
(Refer to table below.)
(Refer to table below.)
---
Chapter 10
10-85

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3g3rv-pdrt2