Appendices

Communications Error Content: Register Number 003D Hex

Bit
0
CRC error (1: error)
1
Incorrect data length (1: error)
2
Not used.
3
Parity error (1: error)
4
Overrun error (1: error)
5
Framing error (1: error)
6
Communications timeover (1: error)
7 to 15
Not used.

10-4-3 Parameter Reading and Writing

The following tables show the SYSDRIVE 3G3MV Inverter parameter classes, instances and
attributes, and the corresponding register numbers. Write and read the various parameters with "1"
as the minimum setting unit. Negative numbers are expressed as two's complements. When param-
eters are written, the settings for parameters that can be written during operation become valid after
the being set in RAM, whereas the settings for parameters that cannot be written during operation,
become valid from the next operation. Send an enter command to save the set data in EEPROM.
Note The 2 register numbers that are different from RS-422/485 communications are indicated by
shading (refer to page 10-39).

Function Group 1 (n001 to n049)

Con-
Regis-
Class 64 (hex)
stant
ter num-
In-
ber
stance
(hex)
n001
0101
01
n002
0102
01
n003
0103
01
n004
0104
01
n005
0105
01
n006
0106
01
n007
0107
01
n008
0108
01
n009
0109
01
n010
010A
01
n011
010B
01
n012
010C
01
Note [ ] values indicate those for 400-V-class Inverters.
Content
Name
At-
tribute
01
Parameter write-prohibit selection/
parameter initialization
02
Control mode selection
03
Run command selection
04
Frequency reference selection
05
Stopping method selection
06
Reverse rotation-prohibit selection
07
STOP Key function selection
08
Frequency reference selection in local
mode
09
Operator frequency setting method
selection
0A
Operation selection at Digital Operator
interruption
0B
Maximum frequency (FMAX)
0C
Maximum voltage (VMAX)
Chapter 10
Setting
Setting
Default
range
unit
setting
0 to 9
1
1
0, 1
1
0
0 to 3
1
0
0 to 9
1
0
0, 1
1
0
0, 1
1
0
0, 1
1
0
0, 1
1
0
0, 1
1
0
0, 1
1
0
50.0 to
0.1 Hz
60.0
400.0
0.1 to
0.1 V
200.0
255.0
[400.0]
[0.1 to
510.0]
Write
during
opera-
tion
No
No
No
No
No
No
No
No
No
No
No
No
10-35