Configurator Settings
Setting Method
Click the Warning Torque Tab in the Edit Device Parameters Window, and set each setting item.
Item
Current 1 (during
Accel/Decel)
Current 2 (during Fre-
quency Agree)
Detection Filter
Status
Note 1. When Current 1 is set to 0.0 (A), the warning torque during acceleration/deceleration is not
detected.
Note 2. When Current 2 is set to 0.0 (A), the warning torque during frequency agreement is not de-
tected.
Note 3. A detection sensitivity level of 5 disables the filter. A detection sensitivity level of 1 uses the
average of 5 sampled current levels (moving average) as the detection value.
7-14
Setting range
0.0 to 6,553.5 (A)
(See note 1.)
0.0 to 6,553.5 (A)
(See note 2.)
level
Detection sensitivity
level
1 (lowest) to
5 (high-
est)
(See note 3.)
Hold or do not hold
Warning Torque Tab
Page in the Edit
Device Parameters
Window
Details
Sets the monitor value (threshold) of the output current
during acceleration or deceleration.
Sets the monitor value (threshold) of the output current
during frequency agreement (while operating at con-
stant speed).
level of
Sets the
sensitivity to prevent detection of val-
ues that temporarily exceed the threshold value.
Selected: Status is maintained when a warning torque
is detected.
Not selected: The status is refreshed every time.