Operating Time Measurement Trigger; Output-To-Input Example - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Configurator Settings
• The combination of start signal (and command) and completion signal for operating time measure-
ment are determined as shown in the following table.
No.
Measurement start condition
00
Multi-function contact output: ON
01
Multi-function output 1: ON
02
Input 2: ON
03
Input 4: ON
04
Input 0 is ON, input 1 is ON, or a forward/reverse
run command is sent from the network.
05
Input 0 is ON, input 1 is ON, or a forward/reverse
run command is sent from the network.
Note 1. The input references in the above table refer to the inputs in the following table. When control
I/O remote I/O is used, the input will be turned ON not only when the terminal's signal is ON,
but also when the corresponding bit is turned ON from remote I/O. (The terminal's ON/OFF
status is logically ORed with the status of the bit sent through remote I/O.)
Name
Input 0
Terminal S1 (multi-function
input 1) status
Input 1
Terminal S2 (multi-function
input 2) status
Input 2
Terminal S3 (multi-function
input 3) status
Input 3
Terminal S4 (multi-function
input 4) status
Input 4
Terminal S5 (multi-function
input 5) status
Input 5
Terminal S6 (multi-function
input 6) status
Note 2. The combination of 00 and 01 is valid when combined with control I/O remote I/O and the
following parameter settings.
3G3MV: When 18 (12 hex) (communications output) is set in n057 and n058 (multi-function
outputs 1 and 2).
3G3RV/3G3PV/3G3FV: When F (not used) is set in H2-01 and H2-02 (multi-function contact
output and multi-function output 1).
Under these conditions, output from the Inverter control terminal can be controlled by com-
munications, and these signals can be used as triggers to start measurement.
Application Example

Output-to-input Example

It is possible to detect deterioration in cylinder operation and estimate expiration of the cylinder's ser-
vice life by using the Inverter's multi-function output to drive the cylinder and inputting the cylinder's
travel completed signal in the multi-function input.
7-22

Operating time measurement trigger

3G3MV
Measurement
completion
condition
Input 4: ON
Input 5: ON
Input 3: ON
Input 5: ON
Input 4: ON
Input 5: ON
3G3RV/3G3PV
Terminal S1 (forward run/
stop) status
Terminal S2 (reverse run/
stop) status
Terminal S3 (multi-function
input selection 1) status
Terminal S4 (multi-function
input selection 2) status
Terminal S5 (multi-function
input selection 3) status
Terminal S6 (multi-function
input selection 4) status
Chapter 7
Remarks
Output to input
Output to input
Input to input
Input to input
Forward/reverse run com-
mand to input
Forward/reverse run com-
mand to input
3G3FV
Terminal 1 (forward run/
stop) status
Terminal 2 (reverse run/
stop) status
Terminal 3 (multi-function
contact input 1) status
Terminal 4 (multi-function
contact input 2) status
Terminal 5 (multi-function
contact input 3) status
Terminal 6 (multi-function
contact input 4) status