Status Signals: Register Number 0020 Hex; Fault Status: Register Number 0021 Hex; Output Power - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Appendices
Class 64
number (hex)
Instance Attribute
00
35
0035
00
36
0036
00
37
0037
00
38
0038
00
39
0039
00
3A
003A
00
3B
003B
00
3C
003C
00
3D
003D
00
---
003E to 00FF

Status Signals: Register Number 0020 Hex

Bit
0
During Run (1: During Run)
1
Forward/reverse operation (1: reverse operation)
2
Inverter ready (1: ready)
3
Fault (1: fault)
4
Data setting error (1: error)
5
Multi-function output 1 (1: ON)
6
Multi-function output 2 (1: ON)
7
Multi-function output 3 (1: ON)
8 to 15
Not used.

Fault Status: Register Number 0021 Hex

Bit
0
OC
1
OV
2
OL2
3
OH
4
Not used.
5
Not used.
6
FBL
7
EF@, STP
8
F@
9
OL1
10
OL3
10-32
Register
Function
Accumulated operating
time
Not used.

Output power

PID feedback
PID input
PID output
Output current
Not used.
Communications error
content
Not used.
Content
Content
Content
Read with 1 (h) = 1 decimal
---
Read with 1 (W) = 100 decimal
Read with +/ − .
Read with 1 (%) = 10 decimal
Maximum frequency corresponds to 100%.
Read with 1 (%) = 10 decimal
Maximum frequency corresponds to 100%.
Read with +/ − .
Read with 1 (%) = 10 decimal
Maximum frequency corresponds to 100%.
Read with +/ − .
Read with 1 (A) = 10 decimal Read with +/ −
---
Refer to the following Communications Error
Content table.
---
Chapter 10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3g3rv-pdrt2

Table of Contents